Page 1 - Maintaining the HRPSU

Part No. 114312 Rev. CNovember 1996 Installing and Maintaining the HRPSU

Page 2

Installing and Maintaining the HRPSU1-4 114312 Rev. C For network devices that use 16-pin cables, you must install a connector adapter to attach the

Page 3 - USA Requirements Only

Overview of the HRPSU 114312 Rev. C 1-5 • Review the installation procedures in Chapter 2. Read all safety sheets included with the shipment, and th

Page 5 - Bay Networks Software License

114312 Rev. C 2-1 Chapter 2Installing the HRPSU This chapter describes• Cabling options for network devices• Mounting the HRPSU in a surface stack o

Page 6 - (continued)

Installing and Maintaining the HRPSU2-2 114312 Rev. C Using One 24-Pin Cable Figure 2-1 shows the cabling between a single 24-pin redundant power con

Page 7 - Chapter 1

Installing the HRPSU 114312 Rev. C 2-3 Installing an Adapter for 16-Pin Cables If your network device uses 16-pin cables, you must install an adapte

Page 8

Installing and Maintaining the HRPSU2-4 114312 Rev. C You can install up to four adapters on the HRPSU; however, only one network device may be attac

Page 9 - HRP0002A

Installing the HRPSU 114312 Rev. C 2-5 Using One 16-Pin Cable Figure 2-3 shows the cabling between a single 16-pin redundant power connector on a ne

Page 10 - Preparing for Installation

Installing and Maintaining the HRPSU2-6 114312 Rev. C Figure 2-4. Cabling with Two 16-Pin Cables Mounting the HRPSU You can mount the HRPSU on a flat

Page 11 - Overview of the HRPSU

Installing the HRPSU 114312 Rev. C 2-7 Figure 2-5. HRPSU Mounted on a Surface To mount the HRPSU under a stack of devices, place the unit on a surfa

Page 12

ii 114312 Rev. C4401 Great America Parkway 8 Federal StreetSanta Clara, CA 95054 Billerica, MA 01821 Copyright © 1988–1996 Bay Networks, Inc. All rig

Page 13 - Installing the HRPSU

Installing and Maintaining the HRPSU2-8 114312 Rev. C Mounting the HRPSU in a Rack This procedure requires• Three hardware packages from the HRPSU sh

Page 14 - Using One 24-Pin Cable

Installing the HRPSU 114312 Rev. C 2-9 Figure 2-6. Locating the Rail Holes 3. Insert each angle bracket inside the rack in the area indicated in Fig

Page 15 - 114312 Rev. C

Installing and Maintaining the HRPSU2-10 114312 Rev. C Figure 2-7. Attaching Angle Brackets Run Boot Diag Local Power Height:5.25 in. (13

Page 16

Installing the HRPSU 114312 Rev. C 2-11 4. Refer to Figure 2-8 and attach each flange to the HRPSU as follows. • When the HRPSU is to be mounted to s

Page 17 - Using One 16-Pin Cable

Installing and Maintaining the HRPSU2-12 114312 Rev. C Figure 2-9. Mounting the HRPSU in an Enclosure Rack 6. Insert a 10-32 screw through each flange

Page 18 - Mounting the HRPSU

Installing the HRPSU 114312 Rev. C 2-13 Installing a Power Supply Module in the HRPSU Power Rack The HRPSU power rack and the power supply modules a

Page 19

Installing and Maintaining the HRPSU2-14 114312 Rev. CConnecting Cables and Switching on PowerWhen you have installed the power supply modules in the

Page 20 - Mounting the HRPSU in a Rack

Installing the HRPSU114312 Rev. C 2-15 8.Verify that the power is on by checking the LED on each HRPSU power supply module being used, and the redunda

Page 22

114312 Rev. C 3-1 Chapter 3Maintaining the HRPSUThe HRPSU requires little maintenance. You should not open the HRPSU chassis. If you have any problems

Page 23

114312 Rev. C iii USA Requirements Only Federal Communications Commission (FCC) Compliance Notice: Radio Frequency Notice This equipment generates,

Page 24

Installing and Maintaining the HRPSU3-2 114312 Rev. C5. Turn on the power supply module’s switch and verify that the green Power OK LED is lighted.Fig

Page 25 - Power OK

114312 Rev. C A-1 Appendix ATechnical SpecificationsTable A-1. Physical SpecificationsHRPSU Power Rack Dimensions: (H) 5.25 in. by (W) 17.5 in. by (D)

Page 26

Installing and Maintaining the HRPSUA-2 114312 Rev. CTable A-4. Electrical SpecificationsElectrical Line frequency: 47 to 63 HzVoltage amperes rating:

Page 27

114312 Rev. C xiii About This GuideThis guide explains how to mount, install, and maintain a Bay Networks™ HRPSU (High Power Redundant Power Supply Un

Page 29 - Chapter 3

114312 Rev. C ixFiguresFigure 1-1. HRPSU (High Power Redundant Power Supply Unit) ...1-1Figure 1-2. HRPSU Power Rack and Po

Page 31 - Technical Specifications

114312 Rev. C xiTablesTable 2-1. Options for Cabling a Network Device ...2-1Table 2-2 Status Indica

Page 33 - About This Guide

114312 Rev. C viiContentsAbout This GuideRelated Documentation ...

Page 34

iv 114312 Rev. C Japan/Nippon Requirements Only Voluntary Control Council for Interference (VCCI) StatementVoluntary Control Council for Interferenc

Page 35 - 114312 Rev. C ix

viii 114312 Rev. CInstalling a Power Supply Module in the HRPSU Power Rack ...2-13Connecting Cables and Switching o

Page 36

114312 Rev. C xv Technical Support and Online ServicesTo ensure comprehensive network support to our customers and partners worldwide, Bay Networks Cu

Page 37 - 114312 Rev. C xi

Installing and Maintaining the HRPSUxvi 114312 Rev. CBay Networks Customer Service If you purchased your Bay Networks product from a distributor or au

Page 38

Technical Support and Online Services114312 Rev. C xvii Bay Networks Information ServicesBay Networks Information Services provide up-to-date support

Page 39 - Contents

Installing and Maintaining the HRPSUxviii 114312 Rev. CSupport Source CDThis CD-ROM -- sent quarterly to all contracted customers -- is a complete Bay

Page 40

Technical Support and Online Services114312 Rev. C xix InfoFACTSInfoFACTS is the Bay Networks free 24-hour fax-on-demand service. This automated syste

Page 42

114312 Rev. C v Bay Networks Software License This Software License shall govern the licensing of all software provided to licensee by Bay Networks

Page 43 - Customer Service FTP

vi 114312 Rev. C Bay Networks Software License (continued) 9. Licensee shall not reverse assemble, reverse compile, or in any way reverse engineer

Page 44 - CompuServe

114312 Rev. C 1-1 Chapter 1Overview of the HRPSU This chapter describes the HRPSU (High Power Redundant Power Supply Unit) power rack and power supp

Page 45 - How to Get Help

Installing and Maintaining the HRPSU1-2 114312 Rev. C The HRPSU supports devices requiring up to 210 watts of power, as well as those with lower powe

Page 46

Overview of the HRPSU 114312 Rev. C 1-3 Hot-swap connectors on each power supply module connect the input and output signals of the power supply to